116 Parameters
06.21 Drive status word 3 Drive status word 3.
This parameter is read-only.
-
0000h…FFFFh Drive status word 1. 1 = 1
06.30 MSW bit 11 selection Selects a binary source whose status is transmitted as bit
11 (User bit 0) of 06.11 Main status word.
Ext ctrl loc
False 0. 0
True 1. 1
Ext ctrl loc Bit 11 of 06.01 Main control word.2
Other [bit] Source selection (see Terms and abbreviations). -
06.31 MSW bit 12 selection Selects a binary source whose status is transmitted as bit
12 (User bit 1) of 06.11 Main status word.
Ext run
enable
False 0. 0
True 1. 1
Ext run enable Status of the external run enable signal (see parameter
20.12 Run enable 1).
2
Other [bit] Source selection (see Terms and abbreviations). -
06.32 MSW bit 13 selection Selects a binary source whose status is transmitted as bit
13 (User bit 2) of 06.11 Main status word.
False
False 0. 0
True 1. 1
Other [bit] Source selection (see Terms and abbreviations). -
06.33 MSW bit 14 selection Selects a binary source whose status is transmitted as bit
14 (User bit 3) of 06.11 Main status word.
False
False 0. 0
True 1. 1
Other [bit] Source selection (see Terms and abbreviations). -
07
07 System info
Drive hardware and firmware information.
All parameters in this group are read-only.
07.03 Drive rating id Type of the drive/inverter unit. -
0... 65535
07.04 Firmware name Firmware identification. -
07.05 Firmware version Version number of the firmware. -
07.06 Loading package
name
Name of the firmware loading package. -
No. Name/Value Description Default
FbEq 16
Bit Name Description
0 DC hold active 1 = DC hold is active
1 Post-magnetizing
active
1 = Post-magnetizing is active
2 Motor pre-heating
active
1 = Motor pre-heating is active
3…15 Reserved