Program features 59
Control interfaces
The number of inputs and outputs depend on the product variant and if the drive is
equipped with any optional I/O extension modules.
S variant:
• 4 x Digital Inputs
• 2 x Digital Inputs/Outputs
• 2 x Analog Inputs
• 1 x Analog Output
• 1 x Relay Output
C variant:
• 2 x Digital Inputs
• 1 x Relay Output
Programmable analog inputs
There are max two programmable analog inputs. Each of the inputs can be
independently set as a voltage (0/2…10 V or -10…10 V) or current (0/4…20 mA)
input by a switch on the control unit. Each input can be filtered, inverted and scaled.
Parameters
Group 12 Standard AI.
Programmable analog outputs
There is max one current (0...20mA) analog output. The output can be filtered,
inverted and scaled.
Parameters
Group 13 Standard AO.
Programmable digital inputs and outputs
There are max four digital inputs, and two digital inputs/outputs (I/O that can be set as
either an input or an output).
Digital input/output DIO1 can be used as a frequency input, DIO2 as a frequency
output.
Parameters
Groups 10 Standard DI, RO, 11 Standard DIO, FI, FO.