200 Parameters
30.30 Overvoltage control Enables the overvoltage control of the intermediate DC
link. Fast braking of a high inertia load causes the voltage
to rise to the overvoltage control limit. To prevent the DC
voltage from exceeding the limit, the overvoltage
controller automatically decreases the braking torque.
Note: If the drive is equipped with a brake chopper and
resistor, or a regenerative supply unit, the controller must
be disabled.
Enable
Disable Overvoltage control disabled. 0
Enable Overvoltage control enabled. 1
30.31 Undervoltage control Enables the undervoltage control of the intermediate DC
link. If the DC voltage drops due to input power cut off, the
undervoltage controller will automatically decrease the
motor torque in order to keep the voltage above the lower
limit. By decreasing the motor torque, the inertia of the
load will cause regeneration back to the drive, keeping the
DC link charged and preventing an undervoltage trip until
the motor coasts to a stop. This will act as a power-loss
ride-through functionality in systems with high inertia,
such as a centrifuge or a fan.
Enable
Disable Undervoltage control disabled. 0
Enable Undervoltage control enabled. 1
31
31 Fault functions
Configuration of external events; selection of behavior of
the drive upon fault situations.
31.01 External event 1
source
Defines the source of external event 1.
See also parameter 31.02 External event 1 type.
0 = Trigger event
1 = Normal operation
Inactive
(true)
Active (false) 0. 0
Inactive (true) 1. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DIO1 Digital input/output DIO1 (11.02 DIO delayed status, bit 0). 10
DIO2 Digital input/output DIO2 (11.02 DIO delayed status, bit 1) 11
Other [bit] Source selection (see Terms and abbreviations). -
31.02 External event 1 type Selects the type of external event 1. Fault
Fault The external event generates a fault. 0
Warning The external event generates a warning. 1
31.03 External event 2
source
Defines the source of external event 2. See also
parameter 31.04 External event 2 type.
For the selections, see parameter 31.01 External event 1
source.
Inactive
(true)
31.04 External event 2 type Selects the type of external event 2.
Fault The external event generates a fault. 0
Warning The external event generates a warning. 1
No. Name/Value Description Default
FbEq 16