82 Program features
Wiring example
The figure below shows a brake control wiring example. The brake control hardware
and wiring is to be sourced and installed by the customer.
WARNING! Make sure that the machinery into which the drive with brake
control function is integrated fulfills the personnel safety regulations. Note that
the frequency converter (a Complete Drive Module or a Basic Drive Module, as
defined in IEC/EN 61800-2), is not considered as a safety device mentioned in the
European Machinery Directive and related harmonized standards. Thus, the
personnel safety of the complete machinery must not be based on a specific
frequency converter feature (such as the brake control function), but it has to be
implemented as defined in the application specific regulations.
The brake is controlled by bit 0 of parameter 44.01 Brake control status. The source
of brake acknowledge (status supervision) is selected by parameter 44.07 Brake
acknowledge selection. In this example,
parameter 10.24 RO1 source is set to Open brake command (ie. bit 0 of 44.01
Brake control status), and
parameter 44.07 Brake acknowledge selection is set to DIO1.
Motor
M
115/230 VAC
Drive control unit
Mechanical brake
Brake control
hardware
Emergency
brake
XRO1
1 NC
2 COM
3 NO
XD24
XDIO
4 +24VD
5 DIO2

Table of Contents

Other manuals for ABB ACS380 Series

Related product manuals