Fault tracing 301
Extension: 2 The ID run cannot be
completed because the
maximum speed setting and/or
calculated field weakening
point is too low.
Check setting of parameters 99.07 Mot
nom voltage, 99.08 Mot nom freq, 99.09
Mot nom speed, 20.01 Maximum speed
and 20.02 Minimum speed. Make sure
that
• 20.01 Maximum speed > (0.55 × 99.09
Mot nom speed) > (0.50 × synchronous
speed),
• 20.02 Minimum speed <
0, and
• supply voltage >
(0.66 × 99.07 Mot nom
voltage).
Extension: 3 The ID run cannot be
completed because the
maximum torque setting is too
low.
Check setting of parameter 99.12 Mot
nom torque and torque limits defined in
parameter group 20 Limits. Make sure
that the active maximum torque (selected
by 20.06 Torq lim sel) > 100%.
Extension: 4 Current measurement
calibration did not finish within
reasonable time.
Contact your local ABB representative.
Extension: 5…8 Internal error. Contact your local ABB representative.
Extension: 9 Asynchronous motors only:
Acceleration did not finish
within reasonable time.
Contact your local ABB representative.
Extension: 10 Asynchronous motors only:
Deceleration did not finish
within reasonable time.
Contact your local ABB representative.
Extension: 11 Asynchronous motors only:
Speed dropped to zero during
ID run.
Contact your local ABB representative.
Extension: 12 Permanent magnet motors
only: First acceleration did not
finish within reasonable time.
Contact your local ABB representative.
Extension: 13 Permanent magnet motors
only: Second acceleration did
not finish within reasonable
time.
Contact your local ABB representative.
Extension: 14…16 Internal error. Contact your local ABB representative.
0018 CURR U2 MEAS
(0x3184)
Measured offset error of U2
output phase current
measurement is too great.
(Offset value is updated during
current calibration.)
Contact your local ABB representative.
0019 CURR V2 MEAS
(0x3185)
Measured offset error of V2
output phase current
measurement is too great.
(Offset value is updated during
current calibration.)
Contact your local ABB representative.
0020 CURR W2 MEAS
(0x3186)
Measured offset error of W2
output phase current
measurement is too great.
(Offset value is updated during
current calibration.)
Contact your local ABB representative.
Code Fault
(fieldbus code)
Cause What to do