Note: If there is a symmetrically constructed grounding conductor on the motor cable in addition to the conductive
shield, connect the grounding conductor to the grounding terminal at the drive and motor ends.
Do not use an asymmetrically constructed motor cable. Connecting its fourth conductor at the motor end in-
creases bearing currents and causes extra wear.
*) Switch-disconnector and separate fuses in frames R9…R11.
■ Layout of the power cable connection terminals and entries (frames
R6 to R8)
The layout of power cable connection terminals and cable entries of the standard drive is
shown below.
Note: You have to remove the “door” fan to get access to the cable terminals and entries
(see Replacing the cabinet “door" fans (page 166)).
Strain relief1
Power cable entries. Conductive sleeve under the
grommet. The grommets are included in IP54 units
only.
2
Control cable entry with EMI conductive cushions.3
PE terminal4
Input power cable terminals L1, L2 and L35
Motor cable terminals U2, V2, W26
Electrical installation 113