Free space requirements
Above *SideFront
inmminmminmm
15.75400--5.91150
* measured from the base plate of the cabinet top.
> 400 mm
(15.75 in.)
IP22/42 IP54
R6…R8: 400 mm (15.75 in.)
R9…R11: 800 mm (31.50 in.)
Losses, cooling data and noise
NoiseHeat dissipa-
tion
Air flowFrameDrive type
dB (A)Wft
3
/minm
3
/h
U
n
= 400 V
67179511301750R6ACS880-07-0105A-3
67194011301750R6ACS880-07-0145A-3
67244011301750R7ACS880-07-0169A-3
67281011301750R7ACS880-07-0206A-3
65380011301750R8ACS880-07-0246A-3
65440011301750R8ACS880-07-0293A-3
6853006771150R9ACS880-07-0363A-3
6865006771150R9ACS880-07-0430A-3
72610218372950R10ACS880-07-0505A-3
72690918372950R10ACS880-07-0585A-3
72862218372950R10ACS880-07-0650A-3
72926418372950R11ACS880-07-0725A-3
721036218372950R11ACS880-07-0820A-3
Technical data 211