EasyManua.ls Logo

ABB ACS880-07 Series - Air Outlet Duct on the Cabinet Roof (Option +C130)

ABB ACS880-07 Series
270 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1
Air inlet area1
Support the plinth of the cabinet all round.
The air duct must be able to supply a sufficient volume of cooling air. See technical data for
the minimum air flow values.
WARNING!
Make sure that the incoming air is sufficiently clean. If not, dust goes into the
cabinet. The outlet filter on the cabinet roof prevents dust from going out. The
collected dust can cause drive malfunction and danger of fire.
Air outlet duct on the cabinet roof (option +C130)
The option adds air outlet ducts to each cubicle of the cabinet line-up. The outlet diameter
(and quantity) of the ducts depend on the cubicle width. The ducts used are from the Veloduct
series by FläktGroup.
ChannelOutlet duct
Cubicle width
(mm)
Recommended
inner diameter
(mm)
Cross-sectional
area (m
2
)
Inner diameter
(mm)
Outer diameter
(mm)
Veloduct type
200.0 200.70.030194200BDEA-6-020300
315.0 315.90.073304310BDEA-6-031400
315.0 315.90.073304310BDEA-6-031500
400.0 401.00.122394400BDEA-6-040600
400.0 401.00.122394400BDEA-6-040700
315.0 315.90.1453043102 × BDEA-6-031800
315.0 315.90.1453043102 × BDEA-6-0311000
The ventilation system must keep the static pressure in the air outlet duct sufficiently below
the pressure of the room where the drive is located in order that the cabinet fans can produce
the required air flow through the cabinet. Make sure that no dirty or moist air is able to flow
backward to the drive in any case, even during off-time or while servicing the drive or the
ventilation system.
Mechanical installation 83
10

Table of Contents

Related product manuals