3. Install the front top profile of the cabinet in reverse order to step 1.
4. Fasten the back mounting screws of the roof.
1
1
2
3
4
Attaching the cabinet to the floor and wall or roof
General rules
The drive must be installed in an upright vertical position.
Leave 400 mm (15.75”) of free space above the basic roof level of the cabinet for cooling.
The cabinet can be installed with its back against a wall (a), or back-to-back with another
unit (b).
Leave some space (w) at the side where the cabinet outmost hinges are to allow the
doors to open sufficiently. The doors must open 120° to allow supply or inverter
moduledrive modulereplacement.
Mechanical installation 77