NoiseAir flowHeat dissipationSine filter typeFrameACS880-
07-…
TotalFilterDriveTotalFilterDrive
dBAm
3
/hm
3
/hm
3
/hkWkWkW
801750*17505.30.94.4B84143V0207S230R80174A-7
801150*11505.60.94.7B84143V0207S230R90210A-7
801150*11506.20.95.3B84143V0207S230R90271A-7
80365070029507.82.25.6NSIN0485-6R100330A-7
80365070029508.72.36.4NSIN0485-6R100370A-7
8036507002950102.47.6NSIN0485-6R100430A-7
80365070029509.83.26.6NSIN0485-6R110470A-7
8036507002950113.67.4NSIN0485-6R110522A-7
80495020002950134.09NSIN0900-6R110590A-7
8051702000317014.94.910NSIN0900-6R110650A-7
8051702000317016.14.911.2NSIN0900-6R110721A-7
* Natural convection
Sine filter is not available for ACS880-07-0302A-5.
Typical power cable sizes
The table below gives copper and aluminum cable types with concentric copper shield for
the drives with nominal current. For the cable sizes accepted by the drive cabinet entries
and connection terminals, see Terminal and entry data for the power cables (page 216).
US
2)
IEC
1)
Frame
size
Drive type
Cu cable typeAl cable typeCu cable type
AWG/kcmil per phasemm
2
mm
2
U
n
= 400 V
13×703×50R6ACS880-07-0105A-3
2/03×1203×95R6ACS880-07-0145A-3
3/03×1503×120R7ACS880-07-0169A-3
250 MCM3×2403×150R7ACS880-07-0206A-3
300 MCM2 × (3×95)2 × (3×70)R8ACS880-07-0246A-3
2 × 3/02 × (3×120)2 × (3×95)R8ACS880-07-0293A-3
2 × 4/02 × (3×185)2 × (3×120)R9ACS880-07-0363A-3
2 × 250 MCM2 × (3×240)2 × (3×150)R9ACS880-07-0430A-3
2×500 MCM or 3×250 MCM3 × (3×150)3 × (3×95)R10ACS880-07-0505A-3
2×600 MCM or 3×300 MCM3 × (3×185)3 × (3×120)R10ACS880-07-0585A-3
2×700 MCM or 3×350 MCM3 × (3×240)3 × (3×150)R10ACS880-07-0650A-3
3×500 MCM or 4×300 MCM4 × (3×185)3 × (3×185)R11ACS880-07-0725A-3
3×600 MCM or 4×400 MCM4 × (3×240)3 × (3×240)R11ACS880-07-0820A-3
3×600 MCM or 4×400 MCM4 × (3×240)3 × (3×240)R11ACS880-07-0880A-3
U
n
= 500 V
13×703×50R6ACS880-07-0096A-5
2/03×953×95R6ACS880-07-0124A-5
214 Technical data