a
b
12
w
> 400 mm (15.75”)
Note 1: Any height adjustment must be done before attaching the cabinet sections to the
floor or to each other. Height adjustment can be done by using metal shims between the
cabinet bottom and floor.
Note 2: Depending on the size of the cabinet, it has either bolt-on lifting eyes, or lifting bars
with lifting holes. If the cabinet is delivered with lifting bars, remove them. Store the bars for
decommissioning. Bolt-on lifting eyes need not be removed unless the holes are used for
attaching the cabinet. Plug any unused holes using the existing bolts and sealing rings
included. Tighten to 70 N·m (52 lbf·ft).
Attaching the cabinet (non-marine units)
Alternative 1 Clamping
1. Insert the clamps (included) into the twin slots along the front and rear edges of the
cabinet frame body and fasten them to the floor with a bolt. The recommended maximum
distance between the clamps in the front edge is 800 mm (31.5”).
2. If floor mounting at the back is not possible, fasten the top of the cabinet to the wall with
L-brackets (not included in the delivery) bolted to the lifting eye/bar holes, and suitable
hardware.