7. Connect the other end of the data cable to connector X110 on the FSO-xx.
8. To complete the installation, refer to the instructions in the user’s manual delivered with
the FSO-xx.
■ Safety functions module FSO-xx beside the ZCU-14 control unit
1.
Stop the drive and do the steps in section Electrical safety precautions (page 18) before
you start the work.
2. Attach the FSO-xx safety functions module to the mounting plate with four screws.
3. Tighten the mounting screw to 0.8 N·m.
Note: The screw tightens the connections and grounds the module. It is essential for
fulfilling the EMC requirements and for proper operation of the module
4. Connect the FSO-xx data cable to FSO-xx connector X110 and to connector X12 on the
control unit.
5. To complete the installation, refer to the instructions in the user’s manual delivered with
the FSO-xx.
Electrical installation 139