UL (NEC) RATINGS
Output ratingsApp.
power
Max.
current
Input
rating
Frame
size
ACS880-
07-…
Heavy-duty useLight-overload use
P
Hd
I
Hd
P
Ld
I
Ld
S
n
I
max
I
1
hpkWAhpkWAkVAAA
300315325400355382442520370R100370A-7
350355360****450400424514520430R100430A-7
450400415500450472562655470R110470A-7
450450455550500528624655522R110522A-7
500500505600560571705800590R110590A-7
600560571****700630630777820650R110650A-7
600560571****700630705862820721R110721A-7
3AXD10000044776
■ Definitions
Nominal voltage of the drive. For the input voltage range, see section Electrical power network
specification (page 224).
U
n
Nominal rms input current
I
1
Nominal output current (available continuously with no over-loading)
I
n
Apparent power in no-overload use
S
n
Typical motor power in no-overload use
P
n
Continuous rms output current allowing 10% overload for 1 minute every 5 minutes.
I
Ld
Typical motor power in light-overload use
P
Ld
Maximum output current. Available for 10 seconds at start, then as long as allowed by drive temper-
ature.
I
max
Continuous rms output current allowing 50% overload for 1 minute every 5 minutes.
I
Hd
* Continuous rms output current allowing 30% overload for 1 minute every 5 minutes.
** Continuous rms output current allowing 25% overload for 1 minute every 5 minutes.
*** Continuous rms output current allowing 40% overload for 1 minute every 5 minutes.
**** Continuous rms output current allowing 44% overload for 1 minute every 5 minutes.
***** Continuous rms output current allowing 45% overload for 1 minute every 5 minutes.
Typical motor power in heavy-duty use
P
Hd
Note 1: The ratings apply at an ambient temperature of 40 °C (104 °F).
Note 2: To achieve the rated motor power given in the table, the rated current of the drive
must be higher than or equal to the rated motor current.
The DriveSize dimensioning tool available from ABB is recommended for selecting the drive,
motor and gear combination.
Note 3 – ACS880-07-0174A-7 amp rating: The drive can deliver 192 A continuously with
no overload.
Note 4 – ACS880-07-0271A-7 power rating: The power rating is as per NEC Table 42.1.
However, the drive can be used for a typical 4-pole motor rated to 300 hp meeting NEMA
MG 1 Table 12-11 minimum efficiency standard (EPAct efficiency electrical motors) if motor
full load current is not more than 271 A.
200 Technical data