Output ratings for special settingsACS880-
07-…
Low noise modeABB sine filterEx motor (ABB Ex motor)
Heavy-
duty
use
Light-
duty
use
Nominal useHeavy-
duty
use
Light-
duty
use
Nominal useHeavy-
duty
use
Light-
duty
use
Nominal use
I
Hd
I
Ld
P
n
I
n
I
Hd
I
Ld
P
n
I
n
I
Hd
I
Ld
P
n
I
n
AAkWAAAkWAAAkWA
839690101839690101981131101190119A-7
84969010190106901121191201101260142A-7
1011161101221121301101371261461321540174A-7
1221311321381371531321611541751601840210A-7
1381691601781611971602071842262002380271A-7
1572222002322042932503032173002503100330A-7
2002502502602603303153402763383153480370A-7
236*280250290300*3503553603153683553780430A-7
2382612502703083493553603353763553880470A-7
2622902503003423883554003704174004310522A-7
3003303153403854364004504494704504850590A-7
350****430400450450*5305005504805555005750650A-7
350****430400450450*5305005504805745005930721A-7
The ratings apply at an ambient temperature of 40 °C (104 °F).
3AXD00000588487
Nominal voltage of the drive
U
n
Continuous rms output current. No overload capability at 40 °C (104 °F)
I
n
Typical motor power in no-overload use.
P
n
Continuous rms output current allowing 10% overload for 1 minute every 5 minutes
I
Ld
Continuous rms output current allowing 50% overload for 1 minute every 5 minutes
I
Hd
* Continuous rms output current allowing 30% overload for 1 minute every 5 minutes.
** Continuous rms output current allowing 25% overload for 1 minute every 5 minutes.
*** Continuous rms output current allowing 40% overload for 1 minute every 5 minutes.
**** Continuous rms output current allowing 44% overload for 1 minute every 5 minutes.
High speed mode
Selection High speed mode of parameter 95.15 Special HW settings improves control
performance at high output frequencies. We recommend it to be selected with output
frequency of 120 Hz and above.
This table gives the drive module ratings for 120 Hz output frequency and the maximum
output frequency for the drive ratings when High speed mode in parameter 95.15 Special
HW settings is enabled.
With output frequencies smaller than the recommended maximum output frequency, the
current derating is less than the values given in the table. Contact ABB for operation above
the recommended maximum output frequency or for the output current derating with output
frequencies above 120 Hz and below the maximum output frequency.
204 Technical data