Fuses (UL)
The drive is equipped with standard UL fuses listed below for branch circuit protection per
NEC. Obey local regulations.
Fuse (one fuse per phase)Input
current
(A)
ACS880-
07-…
UL class /
Size
With option +F289Bussmann
type
VA
Bussmann
type
A
U
n
= 480 V
J/1170M3414160DFJ-250600250960096A-5
J/1170M3416250DFJ-2506002501240124A-5
J/1170M3416250DFJ-3006003001560156A-5
J/1170M4410315DFJ-3006003001800180A-5
J/2170M5408400DFJ-4006004002400240A-5
J/2170M5410500DFJ-4006004002600260A-5
3170M6410630170M64106906303750302A-5
3170M6410630170M64106906303610361A-5
3170M6411700170M64116907004140414A-5
3170M6411700170M64116907004600460A-5
3170M6412800170M64126908005030503A-5
3170M6413900170M64136909005830583A-5
3170M64141000170M641469010006350635A-5
3170M64161250170M641669012507150715A-5
3170M64161250170M641669012508200820A-5
3170M64171400170M641769014008800880A-5
U
n
= 600 V
J/1170M3412100DFJ-250600250610061A-7
J/1170M3414160DFJ-250600250840084A-7
J/1170M3414160DFJ-250600250980098A-7
J/1170M3416250DFJ-2506002501190119A-7
J/1170M3416250DFJ-2506002501420142A-7
J/1170M4410315DFJ-3006003001740174A-7
1170M4410315170M44106903152100210A-7
2170M5410500170M54106905002710271A-7
3170M6410630170M64106906303300330A-7
3170M6410630170M64106906303700370A-7
3170M6411700170M64116907004300430A-7
3170M6412800170M64126908004700470A-7
3170M6412800170M64126908005220522A-7
3170M6413900170M64136909005900590A-7
3170M64141000170M641469010006500650A-7
3170M64161250170M641669012507210721A-7
Technical data 209