For frames R6 to R9: 300 m (984 ft).Maximum recommended
motor cable length
For frames R10 and R11: 500 m (1640 ft).
Note: For frames R6 to R9 with motor cables longer than 150 m (492 ft) and for
frames R10 and R11 with motor cables longer than 100 m (328 ft), the EMC Dir-
ective requirements may not be fulfilled.
Note: Longer cables cause a motor voltage decrease which limits the available
motor power. The decrease depends on the motor cable length and characteristics.
Contact ABB for more information. A sine filter (option +E206) at the drive output
also causes a voltage decrease.
Control unit connection data
See chapter Control units of the drive (page 141).
Efficiency
Approximately 98% at nominal power level.
Protection classes
IP22, IP42, IP54Degrees of protec-
tion(IEC/EN 60529)
(IEC/EN 60529)
UL Type 1, UL Type 1 Filtered, UL Type 12. For indoor use only.Enclosure types (UL50)
IIIOvervoltage category
(IEC/EN 60664-1)
IProtective class
(IEC/EN 61800-5-1)
Ambient conditions
Environmental limits for the drive are given below. The drive is to be used in a heated,
indoor, controlled environment.
Transportation
in the protective package
Storage
in the protective package
Operation
installed for stationary
use
--0…2000 m (0…6562 ft)
above sea level. For alti-
tudes over 2000 m, contact
ABB.
Installation site altitude
Output derated above 1000
m (3281 ft).
-40 to +70 °C-40 to +70 °C0 +40 °C
(+32 +104 °F). No con-
densation allowed.
Air temperature
(-40 to +158 °F)(-40 to +158 °F)
Output derated in the
range +40 +50 °C
(+104 +122 °F).
Technical data 225