Technical data
Contents of this chapter
This chapter contains the technical specifications of the drive, for example, the ratings, fuse
data, sizes and technical requirements, provisions for fulfilling the requirements for CE and
other markings.
Ratings
The nominal ratings for the drives with 50 Hz and 60 Hz supply are given below. The symbols
are described below the table.
IEC Ratings
Output ratingsInput
rating
Frame
size
ACS880-
07-…
Heavy-duty useLight-overload
use
No-overload use
P
Hd
I
Hd
P
Ld
I
Ld
S
n
P
n
I
n
I
max
I
1
kWAkWAkVAkWAAA
U
n
= 400 V
4587551007355105148105R60105A-3
551057513810075145178145R60145A-3
751459016111790169247169R70169A-3
90169110196143110206287206R70206A-3
110206132234170132246350246R80246A-3
132246*160278203160293418293R80293A-3
160293200345251200363498363R90363A-3
200363**200400298250430
1)
545430
1)
R90430A-3
200361250485350250505560505R100505A-3
12