Electrical power network specification
ACS880-07-xxxxx-3 drives: 380…415 V AC 3-phase +10%…-10%. This is indicated
in the type designation label as typical input voltage level 3 ~ 400VAC
Voltage (U
1
)
ACS880-07-xxxxx-5 drives: 380…500 V AC 3-phase +10%…-10%. This is indicated
in the type designation label as typical input voltage levels 3 ~ 400/480/500 V AC
ACS880-07-xxxxx-7 drives: 525…690 V AC 3-phase +10%…-10%. This is indicated
in the type designation label as typical input voltage levels 3 ~ 525/600/690 V AC.
TN (grounded) and IT (ungrounded) systemsNetwork type
Maximum allowable prospective short-circuit current is 65 kA when the input cable
is protected with gG type fuses (IEC 60269) having maximum current rating as
follows:
Short-circuit withstand
strength Icc
(IEC/EN 61439- 1)
400 A for frames R6 to R8
630 A for frame R9
1250 A for frames R10 and R11.
The drive is suitable for use on a circuit capable of delivering not more than 100,000
rms symmetrical amperes at 600 V maximum when the input cable is protected
with T class fuses.
Short-circuit current protec-
tion (UL 508A)
The drive is suitable for use on a circuit capable of delivering not more than 100
kA rms symmetrical amperes at 600 V maximum when the input cable is protected
with T class fuses.
Short-circuit current protec-
tion (CSA C22.2 No. 14-
05)
50/60 Hz. Variation +5% of the nominal frequency.
Frequency (f
1
)
Max. ± 3% of nominal phase-to-phase input voltageImbalance
0.98 (at nominal load)Fundamental power factor
(cos phi
1
)
Motor connection data
Asynchronous AC induction motors, permanent magnet synchronous motors, AC
induction servomotors and ABB synchronous reluctance motors (SynRM motors)
with option +N7502
Motor types
0 to U
1
, 3-phase symmetrical, This is indicated in the type designation label as
typical output voltage level as 3 ~ 0…U
1
, U
max
at the field weakening point
Voltage (U
2
)
0…500 Hz
Frequency (f
2
)
For drives with du/dt filter: 120 Hz (frames R6 to R9), 200 Hz (frames (R10 and
R11)
For drives with sine filter: 120 Hz
See section Ratings (page 197)
Current
For frames R6 to R9: 2.7 kHz (typically)Switching frequency
For frames R10 and R11: 3 kHz (typically)
The switching frequency can vary per frame and voltage. For exact values, contact
your local ABB representative.