If you have a cardiac pacemaker or other electronic medical device, keep away from the
area near motor, drive, and the drive power cabling when the drive is in operation. There
are electromagnetic fields present which can interfere with the function of such devices.
This can cause a health hazard.
ABB recommends against attaching the cabinet by arc welding. If you have to, obey the
welding instructions in the drive manuals.
Note:
The motor cable terminals of the drive are at a dangerous voltage when the input power
is on, regardless of whether the motor is running or not.
When the input power is on, the drive DC bus is at a dangerous voltage.
If brake chopper and resistor are in use, they are at a dangerous voltage. (Option +D150)
(Option +D151).
External wiring can supply dangerous voltages to the relay outputs of the control units
of the drive.
The Safe torque off function does not remove the voltage from the main and auxiliary
circuits. The function is not effective against deliberate sabotage or misuse.
Optical components
WARNING!
Obey these instructions. If you ignore them, damage to the equipment can occur.
Handle the fiber optic cables with care.
When you unplug the fiber optic cables, always hold the connector, not the cable itself.
Do not touch the ends of the fibers with bare hands as the ends are extremely sensitive
to dirt.
Do not bend the fiber optic cables too tightly. The minimum allowed bend radius is 35 mm
(1.4 in).
Printed circuit boards
WARNING!
Use a grounding wrist band when you handle printed circuit boards. Do not touch
the boards unnecessarily. The boards contain components sensitive to electrostatic
discharge.
Grounding
These instructions are for all personnel who are responsible for the grounding of the drive.
WARNING!
Obey these instructions. If you ignore them, injury or death, or equipment
malfunction can occur, and electromagnetic interference can increase.
If you are not a qualified electrical professional, do not do grounding work.
20 Safety instructions