3. The drive is installed according to the instructions given in the appropriate drive manual(s).
4. Maximum motor cable length is 150 meters (492 ft) for frames R6 to R9 and 100 meters
(328 ft) for frames R10 and R11.
WARNING!
A drive of category C3 is not intended to be used on a low-voltage public network
which supplies domestic premises. Radio frequency interference is expected if
the drive is used on such a network.
■ Category C4
The drive complies with the C4 category with these provisions:
1. It is ensured that no excessive emission is propagated to neighboring low-voltage
networks. In some cases, the natural suppression in transformers and cables is sufficient.
If in doubt, the supply transformer with static screening between the primary and
secondary windings can be used.
Equipment6Medium voltage network1
Supply transformer7Neighboring network2
Static screen8Point of measurement3
Drive9Low voltage4
--Equipment (victim)5
2. An EMC plan for preventing disturbances is drawn up for the installation. A template is
available in Technical guide No. 3 EMC compliant installation and configuration for a
power drive system (3AFE61348280 (English)).
3. The motor and control cables are selected, and routed according to the electrical planning
guidelines of the drive. The EMC recommendations are obeyed.
4. The drive is installed according to its installation instructions. The EMC recommendations
are obeyed.
WARNING!
A drive of category C4 is not intended to be used on a low-voltage public network
which supplies domestic premises. Radio frequency interference is expected if
the drive is used on such a network.
Technical data 231