US
2)
IEC
1)
Frame
size
Drive type
Cu cable typeAl cable typeCu cable type
AWG/kcmil per phasemm
2
mm
2
3/03×1503×120R7ACS880-07-0156A-5
250 MCM3×1853×150R7ACS880-07-0180A-5
300 MCM2 × (3×95)2 × (3×70)R8ACS880-07-0240A-5
2 × 2/02 × (3×95)2 × (3×70)R8ACS880-07-0260A-5
2 × 3/02 × (3×120)2 × (3×95)R9ACS880-07-0302A-5
2 × 250 MCM2 × (3×185)2 × (3×120)R9ACS880-07-0361A-5
2 × 250 MCM2 × (3×240)2 × (3×150)R9ACS880-07-0414A-5
2×400 MCM or 3×4/03 × (3×150)3 × (3×95)R10ACS880-07-0460A-5
2×500 MCM or 3×250 MCM3 × (3×150)3 × (3×95)R10ACS880-07-0503A-5
2×600 MCM or 3×300 MCM3 × (3×185)3 × (3×120)R10ACS880-07-0583A-5
2×700 MCM or 3×350 MCM3 × (3×240)3 × (3×150)R10ACS880-07-0635A-5
3×500 MCM or 4×300 MCM4 × (3×185)3 × (3×185)R11ACS880-07-0715A-5
3×600 MCM or 4×400 MCM4 × (3×240)3 × (3×240)R11ACS880-07-0820A-5
3x600 MCM or 4x400 MCM4 × (3×240)3 × (3×240)R11ACS880-07-0880A-5
U
n
= 690 V
43×353×25R6ACS880-07-0061A-7
33×503×35R6ACS880-07-0084A-7
23×703×50R7ACS880-07-0098A-7
1/03×953×70R7ACS880-07-0119A-7
2/03×1203×95 3)R8ACS880-07-0142A-7
4/02 × (3×70)3×120 3)R8ACS880-07-0174A-7
300 MCM2 × (3×95)3×185R9ACS880-07-0210A-7
400 MCM2 × (3×120)3×240R9ACS880-07-0271A-7
2×250 MCM or 3×2/03 × (3×120)2 × (3×120)R10ACS880-07-0330A-7
2×300 MCM or 3×3/03 × (3×120)2 × (3×120)R10ACS880-07-0370A-7
2×350 MCM or 3×4/03 × (3×120)3 × (3×95)R10ACS880-07-0430A-7
2×400 MCM or 3×4/03 × (3×150)3 × (3×95)R11ACS880-07-0470A-7
2×500 MCM or 3×250 MCM3 × (3×185)3 × (3×120)R11ACS880-07-0522A-7
2×600 MCM or 3×300 MCM3 × (3×185)3 × (3×150)R11ACS880-07-0590A-7
2×700 MCM or 3×350 MCM3 × (3×240)3 × (3×150)R11ACS880-07-0650A-7
3×500 MCM or 4×300 MCM4 × (3×185)3 × (3×185)R11ACS880-07-0721A-7
3AXD10000044776
The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder
type trays one on top of the other, ambient temperature 30 °C, PVC insulation, surface
temperature 70 °C (EN 60204-1 and IEC 60364-5-52/2001). For other conditions, size the
cables according to local safety regulations, appropriate input voltage and the load current
of the drive.
The cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire
insulation at 40 °C (104 °F)ambient temperature. Not more than three current-carrying
conductors in raceway or cable or earth (directly buried). For other conditions, size the
Technical data 215