3. Switch on the bus termination on the drive that is farthest from the control panel in the
chain.
• With drives that have the panel mounted on the front cover, move the terminating
switch into the outer position.
• With an FDPI-02 module, move termination switch S2 into the TERMINATED position.
Make sure that bus termination is off on all other drives.
4. On the control panel, switch on the panel bus functionality (Options - Select drive - Panel
bus). The drive to be controlled can now be selected from the list under Options - Select
drive.
If a PC is connected to the control panel, the drives on the panel bus are automatically
displayed in the Drive composer tool.
With twin connectors in the control panel holder:
134 Electrical installation