Fieldbus control through the embedded fieldbus interface (EFB) 611
22.12 Speed ref2
source
EFB ref1 or EFB ref2 Selects a reference received through the
embedded fieldbus interface as speed
reference 2.
TORQUE REFERENCE SELECTION
26.11 Torque ref1
source
EFB ref1 or EFB ref2 Selects a reference received through the
embedded fieldbus interface as torque
reference 1.
26.12 Torque ref2
source
EFB ref1 or EFB ref2 Selects a reference received through the
embedded fieldbus interface as torque
reference 2.
FREQUENCY REFERENCE SELECTION
28.11 Frequency ref1
source
EFB ref1 or EFB ref2 Selects a reference received through the
embedded fieldbus interface as frequency
reference 1.
28.12 Frequency ref2
source
EFB ref1 or EFB ref2 Selects a reference received through the
embedded fieldbus interface as frequency
reference 2.
OTHER SELECTIONS
EFB references can be selected as the source at virtually any signal selector parameter by
selecting Other, then either 03.09 EFB reference 1 or 03.10 EFB reference 2.
CONTROL OF RELAY OUTPUTS, ANALOG OUTPUTS AND DIGITAL INPUT/OUTPUTS
10.24 RO1 source RO/DIO control word
bit0
Connects bit 0 of storage parameter 10.99
RO/DIO control word to relay output RO1.
10.27 RO2 source RO/DIO control word
bit1
Connects bit 1 of storage parameter 10.99
RO/DIO control word to relay output RO2.
10.30 RO3 source RO/DIO control word
bit2
Connects bit 2 of storage parameter 10.99
RO/DIO control word to relay output RO3.
11.05 DIO1 function
11.09 DIO2 function
Output (default) Sets the digital input/output to output mode.
11.06 DIO1 output
source
RO/DIO control word
bit8
Connects bit 8 of storage parameter 10.99
RO/DIO control word to digital input/output
DIO1.
11.10 DIO2 output
source
RO/DIO control word
bit9
Connects bit 9 of storage parameter 10.99
RO/DIO control word to digital input/output
DIO2.
13.12 AO1 source AO1 data storage Connects storage parameter 13.91 AO1 data
storage to analog output AO1.
13.22 AO2 source AO2 data storage Connects storage parameter 13.92 AO2 data
storage to analog output AO2.
Parameter
Setting for
fieldbus control
Function/Information