Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
- / uint16(This parameter is only effective when the drive is the
master on a D2D link. See parameters 60.1 M/F
communication port and 60.3 M/F mode.)
In the master, parameters 60.23 M/F status supervision
sel 1 and 60.24 M/F status supervision sel 2 specify the
followers whose status word is monitored by the
master.
This parameter selects the followers (out of followers
1…16) whose status words are monitored by the
master.
If a follower reports a fault (bit 3 of the status word is
on), the action specified in 60.17 Follower fault action
is taken. Bits 0 and 1 of the status word (ready states)
are handled as defined by 60.18 Follower enable.
Using 60.27 M/F status supv mode sel 1 and 60.28 M/F
status supv mode sel 2, it is possible to define whether
any given follower is only monitored when it is stopped.
Note: Also activate communication supervision for the
same followers in parameter 60.19 M/F comm
supervision sel 1.
The status of communication is shown by 62.37 M/F
communication status 1 and 62.38 M/F communication
status 2.
M/F status
supervision sel 1
60.23
Status of follower 1 is monitored.Follower 1b0
Status of follower 2 is monitored.Follower 2b1
Status of follower 3 is monitored.Follower 3b2
Status of follower 4 is monitored.Follower 4b3
Status of follower 5 is monitored.Follower 5b4
Status of follower 6 is monitored.Follower 6b5
Status of follower 7 is monitored.Follower 7b6
Status of follower 8 is monitored.Follower 8b7
Status of follower 9 is monitored.Follower 9b8
Status of follower 10 is monitored.Follower 10b9
Status of follower 11 is monitored.Follower 11b10
Status of follower 12 is monitored.Follower 12b11
Status of follower 13 is monitored.Follower 13b12
Status of follower 14 is monitored.Follower 14b13
Status of follower 15 is monitored.Follower 15b14
Status of follower 16 is monitored.Follower 16b15
1 = 10000h…FFFFh
496 Parameters