Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0 / real32Defines custom scaling for the parameter 75.11 Pump
speed ref source.
The resulting speed reference is then calculated as
follows:
Used pump speed reference = (75.19 Maximum
production speed *(75.11 Pump speed ref source/75.13
Speed reference scaler).
Note: If the pump speed reference input is used
directly, then set this parameter value to 0.
Speed reference
scaler
75.13
1 = 1 / 1 = 1Speed reference scalar.0...30000
2.00 Hz / real32Defines the speed at which drive begins modulating
upon receiving start command.
Starting speed75.15
10 = 1 Hz / 100 = 1 HzStarting speed.0.00 ... 598.00 Hz
NULL / unit32Defines the source for the speed reference. This should
be used with external control location 2 (EXT2).
Ext2 pump speed ref
src
75.16
0NoneNULL
112.12 AI1 scaled value (page 226).AI1 scaled value
212.22 AI2 scaled value (page 228).AI2 scaled value
43.5 FB A reference 1 (page 179).FB A ref1
53.6 FB A reference 2 (page 179).FB A ref2
83.9 EFB reference 1 (page 179).EFB ref1
93.10 EFB reference 2 (page 179).EFB ref2
7Speed reference is taken from parameter 75.12 Fixed
speed ref.
Fixed speed ref
8Speed reference is taken from Embedded fieldbus
reference 1.
Panel reference
9Speed reference is taken from Embedded fieldbus
reference 1 or from the ACS880 control panel.
Note: The reference from the control panel can be used
only when EFB ref 1 is zero or EFB communication is
lost (see parameter 58.7 Communication diagnostics,
bit 10).
The EFB or panel selection also allows to start and stop
the drive from embedded fieldbus using EFB control
word, bit 3.
EFB or panel
10Speed reference is taken from Fieldbus adapter A
reference 1 or from the ACS880 control panel.
Note: The reference from the control panel can be used
only when 3.5 FB A reference 1 is zero or FBA
communication is lost (see parameter 51.31 D2FBA A
comm status).
The selection FBA or panel also allows to start and stop
the drive from the fieldbus using Fieldbus control word,
bit 3.
FBA or panel
See Terms and abbreviations (page 169).Other [bit]
526 Parameters