Chapter 3: Configuration 3.6 Setting the Configuration
493-0736-11 (6-2) 109
Hold and Reset
By activating the digital input Hold, the block will behave as if Signal
momentarily dropped to zero. No Pulses will be generated, and the Val ue output
will freeze. Also, IPC is unchanged while Hold is active.
By selecting the parameter Reset and pressing OK, the user can reset the block.
Activating the digital input ResetSignal has the same effect. Resetting the block
essentially means setting Val ue = 0.00 and IPC = 0. (Reset empties the tank.)
Hold has lower priority than Reset.
Table 70 Integrator Inputs.
Table 71 Integrator Parameters.
Inputs
Name Connection
Signal Analog input
Hold Digital input
ResetSignal Digital input
Parameters
Name Setting Unit
TimeUnit seconds, minutes
Time Time
min
Time Time
max
seconds
OverflowLimit 1 OverflowLimit 999 999 none
DeadBand 0.0 DeadBand 100.0 %
PositiveOnly Off, On none
Reset Resets IPC and Val ue none