Chapter 3: Configuration 3.6 Setting the Configuration
493-0736-11 (6-2) 129
5 When the ramp reaches the first Breaking Point, it immediately starts to
ramp towards to second Breaking Point, and so on.
Notes:
• Pressing the Up/Down keys while RampDone is False has no effect.
• The values of the outputs RampActive and RampDone change according to the
text above. On the lines where there is no text enclosed in parenthesis, the value
of these outputs remain unchanged.
• The output RampDone is True whenever the controller is in Manual Mode.
• Changing the controller mode from Auto to non-Auto when the ramp is active,
terminates the ramp and freezes the Set Point at the current value. At the same
time RampActive is set to False, and RampDone is set to True.
Table 88 Advanced Set Point Ramp Parameters.
Note: MinValue and MaxValue are set in the Operator block.
Note: TimerTime
Max
always represents 24 hours. When TimeUnit is set to
Minutes, TimerTime
Max
= 1440 and when TimeUnit is set to Seconds,
TimerTime
Max
= 86400.
Parameters
Name Setting Unit
Time1 0 ≤ Time1 ≤ 10000 TimeUnit
Va lu e1 Mi n Val u e ≤ Valu e 1 ≤ MaxValue None
Time2 0 ≤ Time2 ≤ 1440 TimeUnit
Va lu e2 Mi n Val u e ≤ Valu e 2 ≤ MaxValue None
Time3 0 ≤ Time3 ≤ 1440 TimeUnit
Va lu e3 Mi n Val u e ≤ Valu e 3 ≤ MaxValue None
Time4 0 ≤ Time4 ≤ 1440 TimeUnit
Va lu e4 Mi n Val u e ≤ Valu e 4 ≤ MaxValue None
Time5 0 ≤ Time5 ≤ 1440 TimeUnit
Va lu e5 Mi n Val u e ≤ Valu e 5 ≤ MaxValue None