3.6 Setting the Configuration Chapter 3: Configuration
158 493-0736-11 (6-2)
When ManualBehavior is set to TrueManual and the ManualEnable input has the
value True, the Hand key is disabled. If the ManualEnable input is False, the
Hand key is enabled and can toggle the Control Mode.
The transition from Auto to Manual can be made by either the Hand key or the
ManualEnable input. However, the transition from Manual to Auto can be made
only by the Hand key.
Figure 55 ManualBehavior = TrueManual.
DDC
The DDC function has two digital inputs, DDCIncrease and DDCDecrease, and
one parameter DDCTime. The DDCIncrease and DDCDecrease inputs only
control the ControlSignal when the ControlMode is Manual.
Activating DDCIncrease makes the ControlSignal increase; activating
DDCDecrease makes the ControlSignal decrease. The rate at which the
ControlSignal changes when one of these inputs is activated is defined by the
parameter DDCTime.
Activating both DDCIncrease and DDCDecrease has the same effect as having
both inputs deactivated.
ManualEnable Input
Hand key
ManualStatus Output
Not
pressed
True
False
Pressed
Manual
Available in
ECA06 ECA60 ECA600 EMA60
-XX-