3.6 Setting the Configuration Chapter 3: Configuration
78 493-0736-11 (6-2)
The Exp function has one analog input, Signal, and one analog output, Value. It
also holds three analog parameters – the exponential Power, a gain Factor and a
Bias.
Table 23 Exp Inputs.
Table 24 Exp Parameters.
Table 25 Exp Outputs.
Note: If the input is not connected it represents the value 0.0 + Bias in the
calculation.
Inputs
Name Connection
Signal Off, Analog
Parameters
Name Setting Unit
Power 0.00 ≤ Power ≤ 10.00 None
Factor –10.00 ≤ Factor ≤ 10.00 None
Bias –10.00 ≤ Bias ≤ 10.00 None
Outputs
Name Type
Value Analog signal