Chapter 3: Configuration 3.6 Setting the Configuration
493-0736-11 (6-2) 79
Comp
The Comp block is used for flow measurement with pressure and/or temperature
compensation. The block has three analog inputs, P
diff
, P
abs
and T, and one analog
output, Val ue. It also holds seven analog parameters.
Table 26 Comp Inputs.
Inputs
Name Connection
P
diff
Off, Analog
P
abs
Off, Analog
TOff, Analog
Available in
ECA06 ECA60 ECA600 EMA60
--XX
P
diff
P
abs
T
Comp
Va lu e
Value Factor P
diff
P
abs
P
absMax
P
absMin
()P
absMin
+
×
P
orifice
-------------------------------------------------------------------------------------------------------------
T
orifice
273+
TT
max
T
min
()T
min
273++
×
------------------------------------------------------------------------------------
×××
=

Table of Contents