Chapter 3: Configuration 3.6 Setting the Configuration
493-0736-11 (6-2) 83
The output, Status, is True whenever all of the inputs are True. Otherwise Status
is False.
Table 31 And Inputs.
Table 32 And Outputs.
Note: If an input is not connected it represents the value True in the calculation.
Or
Status = Signal1 OR Signal2 OR Signal3 OR Signal4
The Or block has four digital inputs, Signal1, Signal2, Signal3 and Signal4, and
one digital output, Status.
Inputs
Name Connection
Signal1 Off, Digital
Signal2 Off, Digital
Signal3 Off, Digital
Signal4 Off, Digital
Outputs
Name Type
Status Digital
Available in
ECA06 ECA60 ECA600 EMA60
- XXX
Signal1
Signal2
Signal3
Signal4
Or
Status