Chapter 3: Configuration 3.6 Setting the Configuration
493-0736-11 (6-2) 97
Table 55 Level Detector Inputs.
Table 56 Level Detector Parameters.
Table 57 Level Detector Outputs.
Delay
The Delay function has one analog input, Signal, and one analog output, Va l u e . It
also holds one analog parameter, DelayTime.
The input Signal is transferred to the output Va lue with a delay of DelayTime
seconds. DelayTime can be set to a maximum value of DelayTime
Max
seconds.
Inputs
Name Connection
Signal Off, Analog
LoLimitSignal Off, Analog
HiLimitSignal Off, Analog
Parameters
Name Setting Unit
LoLimitValue 0.0 ≤ LoLimitValue ≤ HiLimitValue ≤ 100.0 None
HiLimitValue 0.0 ≤ LoLimitValue ≤ HiLimitValue ≤ 100.0 None
Outputs
Name Type
Status Digital
Available in
ECA06 ECA60 ECA600 EMA60
--22
Signal
Delay
Valu e