Chapter 3: Configuration 3.6 Setting the Configuration
493-0736-11 (6-2) 99
As long as IncSignal is active the output increases at a rate set by the parameter
Time. As long as DecSignal is active the output decreases at a rate set by the
parameter Time.
When TrackEnable is false, the value of the Val ue output is controlled by the
IncSignal and the DecSignal inputs. When activating DecSignal, Val u e will not
decrease below LoLimit, and when activating IncSignal, Val ue will not increase
above HiLimit.
When TrackEnable is true, the value of the TrackSignal input is copied to the
Va lu e output. The IncSignal and DecSignal inputs are disregarded when
TrackEnable is true.
The function of LoLimit and HiLimit always applies.
LoLimit ≤ Val ue ≤
HiLimit
Note: If the inputs (IncSignal and DecSignal) are equal (both False or both True)
the value of the output does not change.