Parameter Values (Range) Unit Step Default Description
Val high high limit -10000.0...10000.0 1 10000 Output value high
alarm limit for su-
pervision
Value high limit -10000.0...10000.0 1 10000 Output value high
warning limit for
supervision
Value low limit -10000.0...10000.0 1 -10000 Output value low
warning limit for
supervision
Value low low limit -10000.0...10000.0 1 -10000 Output value low
alarm limit for su-
pervision
Value deadband 100...100000 1 1000 Deadband configu-
ration value for in-
tegral calculation.
(percentage of dif-
ference between
min and max as
0,001 % s)
3.13.5 Monitored data
Table 62: Monitored data
Name Type Values (Range) Unit Description
AI_DB1 FLOAT32 -10000.0...10000 .0 mA input, Connectors 1-2, reported value
AI_RANGE1 Enum
0=normal
1=high
2=low
3=high-high
4=low-low
mA input, Connectors 1-2, range
AI_DB2 FLOAT32 -10000.0...10000 .0 mA input, Connectors 3-4, reported value
AI_RANGE2 Enum
0=normal
1=high
2=low
3=high-high
4=low-low
mA input, Connectors 3-4, range
AI_DB3 FLOAT32 -10000.0...10000 .0 RTD input, Connectors 5-6-11c, reported
value
AI_RANGE3 Enum
0=normal
1=high
2=low
3=high-high
4=low-low
RTD input, Connectors 5-6-11c, range
AI_DB4 FLOAT32 -10000.0...10000 .0 RTD input, Connectors 7-8-11c, reported
value
AI_RANGE4 Enum
0=normal
1=high
2=low
3=high-high
4=low-low
RTD input, Connectors 7-8-11c, range
Table continues on the next page
Basic functions 1MRS758755 C
112 REC615 & RER615
Technical Manual