Name Type Default Description
CB2_POSOPEN BOOLEAN 0=False Circuit breaker open sta-
tus for bus 2
CB2_POSCLOSE BOOLEAN 0=False Circuit breaker close sta-
tus for bus 2
Table 696: ATSABTC Output signals
Name Type Description
OPEN_CB1 BOOLEAN Circuit breaker open command for bus 1
CLOSE_CB1 BOOLEAN Circuit breaker close command for bus 1
OPEN_CB2 BOOLEAN Circuit breaker open command for bus 2
CLOSE_CB2 BOOLEAN Circuit breaker close command for bus 2
INPRO BOOLEAN Automatic operation in progress
BLKD_AL BOOLEAN Automatic transfer switch blocked alarm
9.5.7 Settings
Table 697: ATSABTC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Main bus priority 1=Bus 1
2=Bus 2
1=Bus 1 Main bus priority (1 or 2)
Operate delay CB tr 0...120000 ms 10 200 Circuit breaker trip delay
Transfer dead time 0...120000 ms 10 100 Transfer dead time for closing of
circuit breaker
Reconnection delay 0...300000 ms 10 60000 Delay for opening of non prioritized
CB
9.5.8 Monitored data
Table 698: ATSABTC Monitored data
Name Type Values (Range) Unit Description
ATSABTC Enum 1=on
2=blocked
3=test
Status
Control functions 1MRS758755 C
698 REC615 & RER615
Technical Manual