Table 716: PHQVVR Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Phase supervision
1=Ph A
2=Ph B
3=Ph A + B
4=Ph C
5=Ph A + C
6=Ph B + C
7=Ph A + B + C
7=Ph A + B + C Monitored voltage
phase
Phase mode
1=Three Phase
2=Single Phase
2=Single Phase Three/Single phase
mode
10.3.9 Monitored data
10.3.9.1 PHQVVR Monitored data
Table 717: PHQVVR Monitored data
Name Type Values (Range) Unit Description
ST_A BOOLEAN
0=False
1=True
Start Phase A
(Voltage Varia-
tion Event in pro-
gress)
ST_B BOOLEAN
0=False
1=True
Start Phase B
(Voltage Varia-
tion Event in pro-
gress)
ST_C BOOLEAN
0=False
1=True
Start Phase C
(Voltage Varia-
tion Event in pro-
gress)
INSTSWELLCNT INT32 0...2147483647 Instantaneous
swell operation
counter
MOMSWELLCNT INT32 0...2147483647 Momentary swell
operation coun-
ter
TEMPSWELLCNT INT32 0...2147483647 Temporary swell
operation coun-
ter
MAXDURS-
WELLCNT
INT32 0...2147483647 Maximum dura-
tion swell opera-
tion counter
INSTDIPCNT INT32 0...2147483647 Instantaneous
dip operation
counter
Table continues on the next page