Name Type Description
MON_ALM BOOLEAN CB 'not operated for long
time' alarm
PRES_ALM BOOLEAN Pressure below alarm level
PRES_LO BOOLEAN Pressure below lockout level
OPENPOS BOOLEAN CB is in open position
INVALIDPOS BOOLEAN CB is in invalid position (not
positively open or closed)
CLOSEPOS BOOLEAN CB is in closed position
7.1.7 Settings
7.1.7.1 SSCBR Non group settings
Table 577: SSCBR Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Acc stop current 5.00...500.00 A 0.01 10.00 RMS current set-
ting below which
engy acm stops
Open alarm time 0...200 ms 1 40 Alarm level setting
for open travel time
in ms
Close alarm time 0...200 ms 1 40 Alarm level Setting
for close travel time
in ms
Spring charge time 0...60000 ms 10 15000 Setting of alarm
for spring charging
time of CB in ms
Alarm Op number 0...99999 1 200 Alarm limit for
number of opera-
tions
Lockout Op num-
ber
0...99999 1 300 Lock out limit for
number of opera-
tions
Current exponent 0.00...2.00 0.01 2.00 Current exponent
setting for energy
calculation
Difference Cor time -10...10 ms 1 5 Corr. factor for
time dif in aux. and
main contacts open
time
Alm Acc currents
Pwr
0.00...20000.00 0.01 2500.00 Setting of alarm
level for accumula-
ted currents power
LO Acc currents
Pwr
0.00...20000.00 0.01 2500.00 Lockout limit set-
ting for accumula-
ted currents power
Directional Coef -3.00...-0.50 0.01 -1.50 Directional coeffi-
cient for CB life cal-
culation
Initial CB Rmn life 0...99999 1 5000 Initial value for the
CB remaining life
Table continues on the next page
1MRS758755 C Condition monitoring functions
REC615 & RER615
Technical Manual
565