ABB Relion REC615 - Technical Data; Autoreclosing DARREC

ABB Relion REC615
869 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Type Values (Range) Unit Description
4=Both Dead
U_DIFF_MEAS FLOAT32 0.00...1.00 xUn Calculated volt-
age amplitude
difference
FR_DIFF_MEAS FLOAT32 0.000...0.100 xFn Calculated volt-
age frequency
difference
PH_DIFF_MEAS FLOAT32 0.00...180.00 deg Calculated volt-
age phase angle
difference
U_DIFF_SYNC BOOLEAN
0=False
1=True
Voltage differ-
ence out of limit
for synchronizing
PH_DIF_SYNC BOOLEAN
0=False
1=True
Phase angle dif-
ference out of
limit for synchro-
nizing
FR_DIFF_SYNC BOOLEAN
0=False
1=True
Frequency differ-
ence out of limit
for synchronizing
SECRSYN Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
9.3.9 Technical data
Table 680: SECRSYN Technical data
Characteristic Value
Operation accuracy Depending on the frequency of the voltage measured: f
n
±1
Hz
Voltage:
±3.0 % of the set value or ±0.01 × U
n
Frequency:
±10 mHz
Phase angle:
±3°
Reset time <50 ms
Reset ratio Typically 0.96
Operate time accuracy in definite time mode ±1.0 % of the set value or ±20 ms
1MRS758755 C Control functions
REC615 & RER615
Technical Manual
655