3.1.16 DNP3 settings
Table 23: DNP3 settings
Parameter Values (Range) Unit Step Default Description
Operation 1=on
5=off
5=off Operation Off / On
Port 1=COM 1
2=COM 2
3=Ethernet - TCP 1
4=Ethernet TCP +UDP 1
3=Ethernet - TCP 1 Communication interface
selection
Unit address 1...65519 1 1 DNP unit address
Master address 1...65519 1 3 DNP master and UR ad-
dress
Mapping select 1...2 1 1 Mapping select
ClientIP 0.0.0.0 IP address of client
TCP port 20000...65535 1 20000 TCP Port used on ether-
net communication
TCP write authority 0=No clients
1=Reg. clients
2=All clients
2=All clients 0=no client controls
allowed; 1=Controls al-
lowed by registered cli-
ents; 2=Controls allowed
by all clients
Link keep-alive 0...65535 s 1 0 Link keep-alive interval
for DNP
Validate master addr 1=Disable
2=Enable
1=Disable Validate master address
on receive
Self address 1=Disable
2=Enable
2=Enable Support self address
query function
Need time interval 0...65535 min 1 30 Period to set IIN need
time bit
Time format 0=UTC
1=Local
1=Local UTC or local. Coordinate
with master.
CROB select timeout 1...65535 s 1 10 Control Relay Output
Block select timeout
Data link confirm 0=Never
1=Only Multiframe
2=Always
0=Never Data link confirm mode
Data link confirm TO 100...65535 ms 1 3000 Data link confirm time-
out
Data link retries 0...65535 1 3 Data link retries count
Data link Rx to Tx de-
lay
0...255 ms 1 0 Turnaround transmission
delay
Data link inter char
delay
0...20 char 1 4 Inter character delay for
incoming messages
Data link frame
length
50...292 bytes 1 292 Data link maximum
frame length
Table continues on the next page
Basic functions 1MRS758755 C
54 REC615 & RER615
Technical Manual