5.3.6.2 TRPPTRC Output signals
Table 527: TRPPTRC Output signals
Name Type Description
TRIP BOOLEAN General trip output signal
CL_LKOUT BOOLEAN Circuit breaker lockout out-
put (set until reset)
5.3.7 Settings
5.3.7.1 TRPPTRC Non group settings (Basic)
Table 528: TRPPTRC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Trip pulse time 20...60000 ms 1 250 Minimum duration
of trip output sig-
nal
Trip output mode
1=Non-latched
2=Latched
3=Lockout
1=Non-latched Select the opera-
tion mode for trip
output
5.3.8 Monitored data
5.3.8.1 TRPPTRC Monitored data
Table 529: TRPPTRC Monitored data
Name Type Values (Range) Unit Description
TRPPTRC Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1MRS758755 C Protection related functions
REC615 & RER615
Technical Manual