Table 99: T_BIN_TCMD output signals
Name Type Description
OUT INT32 Output signal
3.17 Configurable logic blocks
3.17.1 Standard configurable logic blocks
3.17.1.1 OR function block
Function block
Figure 64: Function blocks
Functionality
OR, OR6 and OR20 are used to form general combinatory expressions with Boolean
variables
The O output is activated when at least one input has the value TRUE. The default
value of all inputs is FALSE, which makes it possible to use only the required number
of inputs and leave the rest disconnected.
OR has two inputs, OR6 six and OR20 twenty inputs.
Basic functions
1MRS758755 C
132 REC615 & RER615
Technical Manual