Table 6: Comparison of authority logging levels
Audit trail event Authority logging level
None Configura-
tion change
Setting
group
Setting
group,
control
Settings
edit
All
Configuration change
Firmware change
Firmware change fail
Attached to retrofit
test case
Removed from retro-
fit test case
Setting group remote
Setting group local
Control remote
Control local
Test on
Test off
Reset trips
Setting commit
Time change
View audit log
Login
Logout
Password change
Firmware reset
Violation local
Violation remote
2.5 Communication
Operational information and controls are available through these protocols.
However, some communication functionality, for example, horizontal
communication between the protection relays, is only enabled by the IEC 61850
communication protocol.
The IEC 61850 communication implementation supports all monitoring and control
functions. Additionally, parameter settings, disturbance recordings and fault
records can be accessed using the IEC 61850 protocol. Disturbance recordings
are available to any Ethernet-based application in the IEC 60255-24 standard
COMTRADE file format. The protection relay can send and receive binary signals
from other devices (so-called horizontal communication) using the IEC 61850-8-1
GOOSE profile, where the highest performance class with a total transmission time
of 3 ms is supported. Furthermore, the protection relay supports sending and
receiving of analog values using GOOSE messaging. The protection relay meets
1MRS758755 C
REC615 and RER615 overview
REC615 & RER615
Technical Manual
35