3.1.12 HMI settings
Table 19: HMI settings
Parameter Values (Range) Unit Step Default Description
FB naming conven-
tion
1=IEC61850
2=IEC60617
3=IEC-ANSI
1=IEC61850 FB naming conven-
tion used in IED
Default view
1=Measurements
2=Main menu
3=SLD
1=Measurements LHMI default view
Backlight timeout 1...60 min 1 3 LHMI backlight
timeout
Web HMI mode
1=Active read only
2=Active
3=Disabled
3=Disabled Web HMI function-
ality
Web HMI timeout 1...60 min 1 3 Web HMI login
timeout
SLD symbol format
1=IEC
2=ANSI
1=IEC Single Line Dia-
gram symbol for-
mat
Autoscroll delay 0...30 s 1 0 Autoscroll delay
for Measurements
view
Setting visibility
1=Basic
2=Advanced
1=Basic Setting visibility for
HMI
3.1.13 IEC 60870-5-101/104 settings
Table 20: IEC 60870-5-101/104 settings
Parameter Values (Range) Unit Step Default Description
Operation 1=on 5=off 5=off Selects if this protocol instance is ena-
bled or disabled
Port 1=IEC101 - COM 1
2=IEC101 - COM 2
3=IEC104 - Ethernet
3=IEC104 -
Ethernet
Port selection
ClientIP 0.0.0.0 IP address of the client
TCP Port 0...65535 1 2404 Server TCP port
Start Delay 0...20 char 1 4 Frame start delay for serial communica-
tion
End Delay 0...20 char 1 4 Frame end delay for serial communication
Device Address 1...65535 1 1 Device address
ASDU Address 1...65535 1 1 Common address of ASDU
Link Mode 0=Balanced
1=Unbalanced
0=Balanced Link mode setting
Table continues on the next page
1MRS758755 C Basic functions
REC615 & RER615
Technical Manual
49