14.7 Signal output with high make and carry
Table 757: Signal output with high make and carry
Description Value
1
Rated voltage 250 V AC/DC
Continuous contact carry 5 A
Make and carry for 3.0 s 15 A
Make and carry for 0.5 s 30 A
Breaking capacity when the control-circuit
time constant L/R <40 ms
1 A/0.25 A/0.15 A
Minimum contact load 100 mA at 24 V AC/DC
14.8 Signal outputs and IRF output
Table 758: Signal outputs and IRF output
Description
Value
1
Rated voltage 250 V AC/DC
Continuous contact carry 5 A
Make and carry for 3.0 s 10 A
Make and carry 0.5 s 15 A
Breaking capacity when the control-circuit
time constant L/R <40 ms, at 48/110/220 V
DC
1 A/0.25 A/0.15 A
Minimum contact load 10 mA at 5 V AC/DC
1
X100: SO1
X110: SO1, SO2
X130: SO1, SO2 when REC615 is equipped with BIO0006
1
X100: IRF,SO2
Technical data 1MRS758755 C
854 REC615 & RER615
Technical Manual