EasyManua.ls Logo

ABB Relion REC615 - Signal Outputs and IRF Output; Double-Pole Power Outputs with TCS Function X100: PO3 and PO4

ABB Relion REC615
869 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14.7 Signal output with high make and carry
Table 757: Signal output with high make and carry
Description Value
1
Rated voltage 250 V AC/DC
Continuous contact carry 5 A
Make and carry for 3.0 s 15 A
Make and carry for 0.5 s 30 A
Breaking capacity when the control-circuit
time constant L/R <40 ms
1 A/0.25 A/0.15 A
Minimum contact load 100 mA at 24 V AC/DC
14.8 Signal outputs and IRF output
Table 758: Signal outputs and IRF output
Description
Value
1
Rated voltage 250 V AC/DC
Continuous contact carry 5 A
Make and carry for 3.0 s 10 A
Make and carry 0.5 s 15 A
Breaking capacity when the control-circuit
time constant L/R <40 ms, at 48/110/220 V
DC
1 A/0.25 A/0.15 A
Minimum contact load 10 mA at 5 V AC/DC
1
X100: SO1
X110: SO1, SO2
X130: SO1, SO2 when REC615 is equipped with BIO0006
1
X100: IRF,SO2
Technical data 1MRS758755 C
854 REC615 & RER615
Technical Manual

Table of Contents

Other manuals for ABB Relion REC615

Related product manuals