Table 514: INRPHAR Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
5.1.8 Monitored data
5.1.8.1 INRPHAR Monitored data
Table 515: INRPHAR Monitored data
Name Type Values (Range) Unit Description
INRPHAR Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
5.1.9 Technical data
Table 516: INRPHAR Technical data
Characteristic Value
Operation accuracy
At the frequency f = f
n
Current measurement:
±1.5 % of the set value or ±0.002 × I
n
Ratio I2f/I1f measurement:
±5.0 % of the set value
Reset time
+35 ms / -0 ms
Reset ratio
Typically 0.96
Operate time accuracy +35 ms / -0 ms
5.1.10 Technical revision history
Table 517: INRPHAR Technical revision history
Technical revision Change
B Internal improvement
C Internal improvement
Protection related functions 1MRS758755 C
480 REC615 & RER615
Technical Manual