EasyManua.ls Logo

ABB Relion REC615 - Modbus Settings

ABB Relion REC615
869 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.1.15 Modbus settings
Table 22: Modbus settings
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
5=off Enable or disable
this protocol in-
stance
Port
1=COM 1
2=COM 2
3=Ethernet - TCP 1
3=Ethernet - TCP 1 Port selection for
this protocol in-
stance. Select be-
tween serial and
Ethernet based
communication.
Mapping selection 1...2 1 1 Chooses which
mapping scheme
will be used for this
protocol instance.
Address 1...254 1 1 Unit address
Link mode
1=RTU
2=ASCII
1=RTU Selects between
ASCII and RTU
mode. For TCP, this
should always be
RTU.
TCP port 1...65535 1 502 Defines the listen-
ing port for the
Modbus TCP server.
Default = 502.
Parity
0=none
1=odd
2=even
2=even Parity for the serial
connection.
Start delay 0...20 1 4 Start delay in char-
acter times for seri-
al connection
End delay 0...20 1 4 End delay in charac-
ter times for serial
connections
CRC order
0=Hi-Lo
1=Lo-Hi
0=Hi-Lo Selects between
normal or swap-
ped byte order for
checksum for seri-
al connection. De-
fault: Hi-Lo.
Client IP 0.0.0.0 Sets the IP address
of the client. If set
to zero, connection
from any client is
accepted.
Write authority
0=Read only
1=Disable 0x write
2=Full access
2=Full access Selects the control
authority scheme
Time format
0=UTC
1=Local
1=Local Selects between
UTC and local time
for events and
timestamps.
Event ID selection
0=Address
1=UID
0=Address Selects whether the
events are reported
using the MB ad-
dress or the UID
number.
Event buffering
0=Keep oldest
1=Keep newest
0=Keep oldest Selects whether the
oldest or newest
events are kept in
the case of event
buffer overflow.
Table continues on the next page
Basic functions 1MRS758755 C
52 REC615 & RER615
Technical Manual

Table of Contents

Other manuals for ABB Relion REC615

Related product manuals