Parameter Values (Range) Unit Step Default Description
1=True
CB closed Pos sta-
tus
0=False
1=True
0=False Circuit breaker
closed position sta-
tus
Blk signals CBB1 0...63 1 0 Blocking lines for
CBB1
Blk signals CBB2 0...63 1 0 Blocking lines for
CBB2
Blk signals CBB3 0...63 1 0 Blocking lines for
CBB3
Blk signals CBB4 0...63 1 0 Blocking lines for
CBB4
Blk signals CBB5 0...63 1 0 Blocking lines for
CBB5
Blk signals CBB6 0...63 1 0 Blocking lines for
CBB6
Blk signals CBB7 0...63 1 0 Blocking lines for
CBB7
Str 2 delay shot 1 0...300000 ms 10 0 Delay time for
start2, 1st reclose
Str 2 delay shot 2 0...300000 ms 10 0 Delay time for
start2 2nd reclose
Str 2 delay shot 3 0...300000 ms 10 0 Delay time for
start2 3rd reclose
Str 2 delay shot 4 0...300000 ms 10 0 Delay time for
start2, 4th reclose
Str 3 delay shot 1 0...300000 ms 10 0 Delay time for
start3, 1st reclose
Str 3 delay shot 2 0...300000 ms 10 0 Delay time for
start3 2nd reclose
Str 3 delay shot 3 0...300000 ms 10 0 Delay time for
start3 3rd reclose
Str 3 delay shot 4 0...300000 ms 10 0 Delay time for
start3, 4th reclose
Str 4 delay shot 1 0...300000 ms 10 0 Delay time for
start4, 1st reclose
Str 4 delay shot 2 0...300000 ms 10 0 Delay time for
start4 2nd reclose
Str 4 delay shot 3 0...300000 ms 10 0 Delay time for
start4 3rd reclose
Str 4 delay shot 4 0...300000 ms 10 0 Delay time for
start4, 4th reclose
9.4.9 Monitored data
9.4.9.1 DARREC Monitored data
Table 690: DARREC Monitored data
Name Type Values (Range) Unit Description
DISA_COUNT BOOLEAN
0=False
1=True
Signal for coun-
ter disabling
FRQ_OPR_CNT INT32 0...2147483647 Frequent opera-
tion counter
Table continues on the next page
1MRS758755 C Control functions
REC615 & RER615
Technical Manual
687