Parameter Values (Range) Unit Step Default Description
Frq Op counter lim-
it
0...250 1 0 Frequent operation
counter lockout
limit
Frq Op counter
time
1...250 min 1 1 Frequent operation
counter time
Frq Op recovery
time
1...250 min 1 1 Frequent operation
counter recovery
time
Auto init 0...63 1 0 Defines INIT lines
that are activated
at auto initiation
Table 689: DARREC Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Manual close mode
0=False
1=True
0=False Manual close mode
Wait close time 50...10000 ms 50 250 Allowed CB closing
time after reclose
command
Max wait time 100...1800000 ms 100 10000 Maximum wait time
for BLK_RECL_T re-
lease
Max trip time 100...10000 ms 100 10000 Maximum wait time
for deactivation of
protection signals
Max Thm block
time
100...1800000 ms 100 10000 Maximum wait time
for thermal block-
ing signal deactiva-
tion
Cut-out time 0...1800000 ms 100 10000 Cutout time for
protection coordi-
nation
Dsr time shot 1 0...10000 ms 100 0 Discrimination time
for first reclosing
Dsr time shot 2 0...10000 ms 100 0 Discrimination time
for second reclos-
ing
Dsr time shot 3 0...10000 ms 100 0 Discrimination time
for third reclosing
Dsr time shot 4 0...10000 ms 100 0 Discrimination time
for fourth reclosing
Auto wait time 0...60000 ms 10 2000 Wait time for re-
closing condition
fullfilling
Auto lockout reset
0=False
1=True
1=True Automatic lockout
reset
Protection crd limit 1...5 1 1 Protection coordi-
nation shot limit
Protection crd
mode
1=No condition
2=AR inoperative
3=CB close manual
4=AR inop, CB man
5=Always
4=AR inop, CB man Protection coordi-
nation mode
Control line 0...63 1 63 Control line, de-
fines INIT inputs
which are protec-
tion signals
Enable shot jump
0=False
1=True Enable shot jump-
ing
Table continues on the next page
Control functions 1MRS758755 C
686 REC615 & RER615
Technical Manual