Parameter Values (Range) Unit Step Default Description
3=On
Close pulse time 10...10000 ms 10 200 CB close pulse time
Reclaim time 100...1800000 ms 100 10000 Reclaim time
Terminal priority
1=None
2=Low (follower)
3=High (master)
1=None Terminal priority
Synchronisation set 0...127 1 0 Selection for syn-
chronizing require-
ment for reclosing
Auto initiation cnd
1=Not allowed
2=When sync fails
3=CB doesn't close
4=Both
2=When sync fails Auto initiation con-
dition
Tripping line 0...63 1 0 Tripping line,
defines INIT in-
puts which cause
OPEN_CB activa-
tion
Fourth delay in
SOTF
0=False
1=True
0=False Sets 4th delay into
use for all DEL_IN-
IT signals during
SOTF
First reclose time 0...300000 ms 10 5000 Dead time for CBB1
Second reclose
time
0...300000 ms 10 5000 Dead time for CBB2
Third reclose time 0...300000 ms 10 5000 Dead time for CBB3
Fourth reclose time 0...300000 ms 10 5000 Dead time for CBB4
Fifth reclose time 0...300000 ms 10 5000 Dead time for CBB5
Sixth reclose time 0...300000 ms 10 5000 Dead time for CBB6
Seventh reclose
time
0...300000 ms 10 5000 Dead time for CBB7
Init signals CBB1 0...63 1 0 Initiation lines for
CBB1
Init signals CBB2 0...63 1 0 Initiation lines for
CBB2
Init signals CBB3 0...63 1 0 Initiation lines for
CBB3
Init signals CBB4 0...63 1 0 Initiation lines for
CBB4
Init signals CBB5 0...63 1 0 Initiation lines for
CBB5
Init signals CBB6 0...63 1 0 Initiation lines for
CBB6
Init signals CBB7 0...63 1 0 Initiation lines for
CBB7
Shot number CBB1 0...5 1 0 Shot number for
CBB1
Shot number CBB2 0...5 1 0 Shot number for
CBB2
Shot number CBB3 0...5 1 0 Shot number for
CBB3
Shot number CBB4 0...5 1 0 Shot number for
CBB4
Shot number CBB5 0...5 1 0 Shot number for
CBB5
Shot number CBB6 0...5 1 0 Shot number for
CBB6
Shot number CBB7 0...5 1 0 Shot number for
CBB7