LED indication control is preconfigured in a such way that all the protection
function general start and operate signals are combined with this function
(available as output signals OUT_START and OUT_OPERATE). These signals are
always internally connected to Start and Trip LEDs. LEDPTRC collects and combines
phase information from different protection functions (available as output signals
OUT_ST_A /_B /_C and OUT_OPR_A /_B /_C). There is also combined earth fault
information collected from all the earth-fault functions available in the relay
configuration (available as output signals OUT_ST_NEUT and OUT_OPR_NEUT).
3.4 Programmable LEDs
3.4.1 Function block
Figure 13: Function block
3.4.2 Functionality
The programmable LEDs reside on the right side of the display on the LHMI.
1MRS758755 C
Basic functions
REC615 & RER615
Technical Manual
63